Voltage tester WEGA 2 IEC62271-213

Voltage tester WEGA 2 IEC62271-213

Horstmann

SKU:512800124

In stock

View full details

You are not logged in and therefore do not see your prices.

Integrated Three-Phase Voltage Detecting System — Wega 2

The Wega 2 is an integrated three-phase voltage detecting system from HORSTMANN, developed in accordance with IEC 62271-213. The device displays medium voltage phase-selectively via an LCD screen (arrow, dot, and tool symbols) and LED indicators showing V=0 and V≠0. Wega 2 provides information about the voltage status both locally and via electrical outputs for remote signaling.

Functions and Behavior

  • Phase-selective display of medium voltage on LCD and LED indicators.
  • Two independent changeover relay contacts for remote signaling and switching on/off.
  • Built-in front panel test enabling verification of display in installed and de-energized condition.
  • Support for shielded and unshielded connection cables with flat-pin or compact (AMP) connectors.
  • Three LRM measuring sockets (one per phase) plus one ground socket for connecting measuring cables.
  • Full LRM interface in accordance with IEC 62271-213 for use with Orion 3.1 / M1 / LCD.

Typical Applications

  • Display of medium voltage phase-selectively in installation contexts where phase-specific information is required.
  • Remote signaling and secure switching on/off logic via the two independent relay contacts.
  • Verification of display function via the built-in front panel test in installed and de-energized condition.

Documentation

Further information and product specifications can be found on the manufacturer's product page. Source: Horstmann product page

Specifications

  • Product: Wega 2 (integrated three-phase voltage detecting system).
  • Manufacturer: HORSTMANN (manufacturer stated).
  • Standard: IEC 62271-213.
  • Indication: LCD (arrows, dot, tool symbols) and LED (V=0, V≠0).
  • Relay/LED supply: 24–230 V AC/DC.
  • Nominal voltage: from 1 kV.
  • Nominal frequency: 50–60 Hz.
  • Interfaces: 3 LRM measuring sockets + 1 ground socket; LRM socket spacing 14 mm, with sealed dust cap.
  • Connection: Flat-pin or compact (AMP) connector / shielded or unshielded cable.
  • Housing: Polycarbonate, IP54.
  • Temperature range: −40 °C to +75 °C.
  • Other: Tool-free mounting/dismounting; low installation depth 48 mm; two independent relay contacts; full LRM interface.

Content generated using AI – we reserve the right for errors.